Size any room in BTU and tons — with oversize warnings that save comfort.
📏 Rule of thumb: 20 BTU per sq ft at 8 ft ceilings. An oversized unit short-cycles — it cools the air fast but never runs long enough to dehumidify, so do not round a small room up to the next size.
The BTU Calculator is based on the following formula:
Base = Area × 20 × (Ceiling ÷ 8) Adjusted = Base × (1 + Sun% + TopFloor%) Total = Adjusted + 600 × (Occupants − 2) + Kitchen (4,000) BTU = Total rounded to the nearest 500 Tons = BTU ÷ 12,000 kW = BTU × 0.000293071
Variables: Area = Room floor area (sq ft) Ceiling = Ceiling height (ft, 8 ft is the baseline) Sun% = Sun exposure adjustment (−0.10 shaded, 0 average, +0.10 very sunny) TopFloor% = +0.10 if the room has an attic or roof above Occupants = People regularly in the room (first two add nothing) Kitchen = +4,000 BTU for kitchens (DOE guidance) Tons = Cooling capacity in refrigeration tons (12,000 BTU/hr each)
The 20 BTU per sq ft baseline assumes 8 ft ceilings; higher ceilings scale air volume by Ceiling ÷ 8. Sun and floor level apply to the base, people and kitchen add fixed amounts, and the result rounds to 500 BTU steps — the increments window units and mini-splits are sold in.
Worked example: Step 1: Area = 350 sq ft, ceiling = 9 ft, very sunny (+0.10), top floor (+0.10), 3 occupants, not a kitchen. Step 2: Base = 350 × 20 × (9 ÷ 8) = 7,875 BTU. Step 3: Adjusted = 7,875 × 1.20 = 9,450 BTU. Step 4: Total = 9,450 + 600 × (3 − 2) = 10,050 → rounds to 10,000 BTU. Step 5: Tons = 10,000 ÷ 12,000 = 0.83; kW = 10,000 × 0.000293071 ≈ 2.9 kW. Result: a 10,000 BTU (0.83-ton) unit — the tool shows exactly these figures.
The 20 BTU/ft² baseline assumes an 8 ft ceiling, average insulation, and moderate sun — conditions where a 350 ft² room needs about 7,000 BTU/hr. Vaulted ceilings add air volume, so the calculator scales by height ÷ 8: a 10 ft ceiling adds 25% to the base load before anything else.
Heavy shade trims 10% and a baking south or west exposure adds 10%; a top floor with an attic roof above adds another 10% because the ceiling radiates stored heat all afternoon. Each person beyond two adds roughly 600 BTU (a human at rest releases the heat of an old incandescent bulb), and a kitchen adds about 4,000 BTU per DOE guidance.
An oversized unit drops the air temperature in minutes, satisfies the thermostat, and shuts off before it has condensed moisture out of the air. The result is a cold, clammy room — short-cycling also wears the compressor. If your corrected load is more than ~30% above the area-only baseline, insulation, window film, or shade usually beat the next size up.
Central and mini-split systems are sold in tons: 12,000 BTU/hr per ton, so a 24,000 BTU result is a 2-ton unit. Engineers convert with 1 ton ≈ 3.52 kW of cooling. Window units stay labeled in BTU, which is why this calculator shows both.